25 / 101 page ![]() Dual RPM-Based PWM Fan Controller with Hardware Thermal Shutdown Datasheet SMSC EMC2104 25 Revision 1.74 (05-08-08) DATASHEET 5.2 Fan Control Modes of Operation The EMC2104 has four modes of operation for each fan driver. Each mode of operation uses the Ramp Rate control and Spin Up Routine. 1. Direct Setting Mode- in this mode of operation, the user directly controls the fan drive setting. Updating the Fan Driver Setting Register (see Section 6.20) will instantly update the fan drive. Ramp Rate control is optional and enabled via the EN_RRC bits. This is the default mode. The Direct Setting Mode is enabled by clearing the LUT_LOCK bit in the Look Up Table Configuration Register (see Section 6.32) while the TACH / DRIVE bit is set to ‘0’. Whenever the Direct Setting Mode is enabled the current drive will be changed to what was last written into the Fan Driver Setting Register. 2. Fan Speed Control Mode (FSC) - in this mode of operation, the user determines a target tachometer count and the drive setting is automatically updated to achieve this target speed. The algorithm uses the Spin Up Routine and has user definable ramp rate controls. This mode is enabled by clearing the LUT_LOCK bit in the Look Up Table (LUT) Configuration Register and setting the EN_ALGO bit in the Fan Configuration Register. 3. Using the Look Up Table with Fan Drive Settings (Direct Setting w/ LUT Mode) - In this mode of operation, the user programs the Look Up Table with fan drive settings and corresponding temperature thresholds. The fan drive is set based on the measured temperatures and the corresponding drive settings. Ramp Rate control is optional and enabled via the EN_RRC bits. This mode is enabled by programming the Look Up Table then setting the LUT_LOCK bit while the TACH / DRIVE bit is set to ‘1’. The TACH / DRIVE bit in the Look Up Table Configuration Register MUST be set to ‘1’ or the fan drive settings will be incorrectly set. Setting this bit to ‘1’ ensures the settings will be PWM settings. 4. Using the Look Up Table with RPM Target Settings (FSC w/ LUT Mode) - In this mode of operation, the user programs the Look Up Table with TACH Target values and corresponding temperature thresholds. The TACH Target will be set based on the measured temperatures and the corresponding target settings. The fan drive settings will be determined automatically based on the RPM based Fan Speed Control Algorithm This mode is enabled by programming the Look Up Table then setting the LUT_LOCK bit while the TACH / DRIVE bit is set to ‘0’ 83 115 698 115 147 7870 84 116 750 116 148 9090 85 117 787 117 149 10700 86 118 845 118 150 12700 87 119 909 119 151 15800 88 120 953 120 152 20500 89 121 1020 121 153 29400 90 122 1100 122 154 49900 91 123 1150 60 92 Open Table 5.2 TRIP_SET Resistor Setting (continued) TTRIP (°C) LOW RANGE TTRIP (°C) HIGH RANGE RSET (1%) TTRIP (°C) LOW RANGE TTRIP (°C) HIGH RANGE RSET (1%) |
|
Lien URL |
| ALLDATASHEET vous a-t-il été utile ? [ DONATE ] |
À propos de Alldatasheet | Publicité | Contactez-nous | Politique de confidentialité | Lien vers la fiche technique | Echange de liens | Fabricants All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |