2 / 4 page ![]() MODEL: R3Y-YS4 R3Y-YS4 SPECIFICATIONS ES-8961 Rev.10 Page 2/4 https://www.m-system.co.jp/ STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 RoHS Directive FUNCTIONS ■OUTPUT HOLD or OUTPUT OFF In normal conditions, the module outputs the signal from the preferred bus A. When an error is detected, the output is switched to the data from the bus B. •Output Hold If both are in error, the module holds the signal and stands by until one of the communications recovers. •Output OFF If both are in error, the module outputs -15 % and stands by until one of the communications recovers. At the startup, it outputs -15 % until the communication is established and normal data is received. EXTERNAL VIEW B 20 A 20 B 1 A 1 RUN LED ERR LED Output Connector ■ FRONT VIEW • Pin Assignment ■ SIDE VIEW SW3 4 3 2 1 Output Hold |
|
|
Lien URL |
| ALLDATASHEET vous a-t-il été utile ? [ DONATE ] |
À propos de Alldatasheet | Publicité | Contactez-nous | Politique de confidentialité | Lien vers la fiche technique | Echange de liens | Fabricants All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|