IM1-22EX-R
AI

The **IM1-22EX-R** is a high-performance, 2-channel isolating switching amplifier manufactured by **Turck**. It is designed to act as an interface between sensors located in hazardous (Ex) areas and control systems in safe areas.
---
## 1. Core Technical Specifications
| Feature | Specification |
| :--- | :--- |
| **Channels** | 2-Channel |
| **Supply Voltage** | 20…250 VAC / 20…125 VDC |
| **Input Signals** | NAMUR Sensors or Mechanical Contacts |
| **Output Type** | 2 x Relay (Changeover/SPDT) |
| **Switching Frequency** | ≤ 10 Hz |
| **Mounting** | DIN Rail (35 mm) |
| **Protection Class** | IP20 |
---
## 2. Key Electronic Components & Functions
### A. Input Stage (Ex-Side)
The device is intrinsically safe. It provides a current-limited and voltage-limited signal to sensors located in potentially explosive atmospheres.
- **NAMUR Compatibility:** It monitors the current consumption of the sensor (approx. 1mA vs 2.2mA) to determine "ON" or "OFF" states.
- **Line Monitoring:** It features integrated wire-break and short-circuit detection.
### B. Galvanic Isolation
This is the "core" electronic function of the IM1-22EX-R. It provides 3-way isolation between:
1. **Input and Output**
2. **Input and Power Supply**
3. **Output and Power Supply**
This prevents high-voltage surges from the power grid or the control side from reaching the hazardous area.
### C. Output Stage (Relays)
The output utilizes **Electromechanical Relays**.
- **Contact Type:** Changeover (SPDT) contacts.
- **Switching Capacity:** Typically up to 250 VAC / 2 A.
- **Mode Selection:** Users can configure the output behavior (Normally Open or Normally Closed) via DIP switches on the front of the unit.
---
## 3. Configuration & Diagnostics
The device features physical switches and LED indicators to manage electronic logic:
1. **DIP Switches:**
* **NO/NC:** Selects the output relay logic (Normally Open or Normally Closed).
* **LM:** Activates or deactivates Line Monitoring (error detection).
2. **LED Status Indicators:**
* **Green:** Power supply is active.
* **Yellow:** Status of the output relay (Channel 1 and 2).
* **Red:** Error detected (Wire-break or Short-circuit).
---
## 4. Wiring Diagram Overview
```text
[ Hazardous Area ] <----------> [ Safe Area ]
NAMUR Sensor 1 ----| 1 2 |---- Relay Output 1
NAMUR Sensor 2 ----| 3 4 |---- Relay Output 2
| |
| Power|---- 20...250 VAC/VDC
```
- ⤷
What are the specific wiring requirements for using mechanical contacts instead of NAMUR sensors?
- ⤷ How does the IM1-22EX-R handle line monitoring for short circuits?
- ⤷ What is the difference between the IM1-22EX-R and the IM1-12EX-R models?